  "reviewed": "2026-10-27",
  "prepared": "2026-10-29",
  "classification": "Synthetic example. Not a customer result.",
  "limits": [
    "Results depend on the stated synthetic assumptions, applicable boundaries and complete distinct commitments.",
    "No customer validation, production deployment, engineering approval, operating authorization or financial outcome is established.",
    "No maximum MW, safe shorter duration, repeat-cycle or annual availability conclusion.",
    "Unknown does not mean zero physical capacity. Electrical and thermal margins are not added."
  ],
  "source_explanation": "Selected values checked against retained reviewed assessment outputs. This is a readable public extract, not a runtime or complete replay package.",
  "case": {
    "example": "Holding A coupled extension",
    "result": {
      "electrical": "Supported",
      "thermal": "Not supported",
      "combined": "Not supported"
    },
    "period": {
      "end": "2026-10-26T15:00:00+00:00",
      "start": "2026-10-26T09:00:00+00:00"
    },
    "input_basis": "Synthetic within-interval upper bounds, not energy-derived averages or instantaneous peaks.",
    "boundary": "One import-only grid service and one internal electrical section; no embedded generation or storage.",
    "intervals": [
      {
        "start": "2026-10-26T09:00:00+00:00",
        "end": "2026-10-26T10:00:00+00:00",
        "existing_electrical_kw": 3100,
        "added_electrical_kw": 900,
        "added_it_electrical_kw": 720,
        "added_cooling_electrical_kw": 130,
        "added_other_electrical_kw": 50,
        "grid_limit_electrical_kw": 6000,
        "protected_grid_electrical_kw": 400,
        "section_limit_electrical_kw": 6700,
        "protected_section_electrical_kw": 150,
        "grid_margin_after_protection_electrical_kw": 1600,
        "section_margin_after_protection_electrical_kw": 2550
      },
      {
        "start": "2026-10-26T10:00:00+00:00",
        "end": "2026-10-26T11:00:00+00:00",
        "existing_electrical_kw": 3450,
        "added_electrical_kw": 900,
        "added_it_electrical_kw": 720,
        "added_cooling_electrical_kw": 130,
        "added_other_electrical_kw": 50,
        "grid_limit_electrical_kw": 6000,
        "protected_grid_electrical_kw": 400,
        "section_limit_electrical_kw": 6700,
        "protected_section_electrical_kw": 150,
        "grid_margin_after_protection_electrical_kw": 1250,
        "section_margin_after_protection_electrical_kw": 2200
      },
      {
        "start": "2026-10-26T11:00:00+00:00",
        "end": "2026-10-26T12:00:00+00:00",
        "existing_electrical_kw": 3800,
        "added_electrical_kw": 1000,
        "added_it_electrical_kw": 820,
        "added_cooling_electrical_kw": 130,
        "added_other_electrical_kw": 50,
        "grid_limit_electrical_kw": 6000,
        "protected_grid_electrical_kw": 400,
        "section_limit_electrical_kw": 6700,
        "protected_section_electrical_kw": 150,
        "grid_margin_after_protection_electrical_kw": 800,
        "section_margin_after_protection_electrical_kw": 1750
      },
      {
        "start": "2026-10-26T12:00:00+00:00",
        "end": "2026-10-26T13:00:00+00:00",
        "existing_electrical_kw": 4020,
        "added_electrical_kw": 1000,
        "added_it_electrical_kw": 820,
        "added_cooling_electrical_kw": 130,
        "added_other_electrical_kw": 50,
        "grid_limit_electrical_kw": 6000,
        "protected_grid_electrical_kw": 400,
        "section_limit_electrical_kw": 6700,
        "protected_section_electrical_kw": 150,
        "grid_margin_after_protection_electrical_kw": 580,
        "section_margin_after_protection_electrical_kw": 1530
      },
      {
        "start": "2026-10-26T13:00:00+00:00",
        "end": "2026-10-26T14:00:00+00:00",
        "existing_electrical_kw": 3700,
        "added_electrical_kw": 1000,
        "added_it_electrical_kw": 820,
        "added_cooling_electrical_kw": 130,
        "added_other_electrical_kw": 50,
        "grid_limit_electrical_kw": 6000,
        "protected_grid_electrical_kw": 400,
        "section_limit_electrical_kw": 6700,
        "protected_section_electrical_kw": 150,
        "grid_margin_after_protection_electrical_kw": 900,
        "section_margin_after_protection_electrical_kw": 1850
      },
      {
        "start": "2026-10-26T14:00:00+00:00",
        "end": "2026-10-26T15:00:00+00:00",
        "existing_electrical_kw": 3250,
        "added_electrical_kw": 900,
        "added_it_electrical_kw": 720,
        "added_cooling_electrical_kw": 130,
        "added_other_electrical_kw": 50,
        "grid_limit_electrical_kw": 6000,
        "protected_grid_electrical_kw": 400,
        "section_limit_electrical_kw": 6700,
        "protected_section_electrical_kw": 150,
        "grid_margin_after_protection_electrical_kw": 1450,
        "section_margin_after_protection_electrical_kw": 2400
      }
    ],
    "next_action": "Obtain the shared heat-rejection rating at the actual conditions, shared-user allocations and reserve basis before separately evaluating an alternative.",
    "thermal_intervals": [
      {
        "start": "2026-10-26T09:00:00+00:00",
        "end": "2026-10-26T10:00:00+00:00",
        "heat_demand_thermal_kw": 4000,
        "shared_capacity_thermal_kw": 6200,
        "thermal_margin_kw": 2200
      },
      {
        "start": "2026-10-26T10:00:00+00:00",
        "end": "2026-10-26T11:00:00+00:00",
        "heat_demand_thermal_kw": 4350,
        "shared_capacity_thermal_kw": 6000,
        "thermal_margin_kw": 1650
      },
      {
        "start": "2026-10-26T11:00:00+00:00",
        "end": "2026-10-26T12:00:00+00:00",
        "heat_demand_thermal_kw": 4800,
        "shared_capacity_thermal_kw": 5900,
        "thermal_margin_kw": 1100
      },
      {
        "start": "2026-10-26T12:00:00+00:00",
        "end": "2026-10-26T13:00:00+00:00",
        "heat_demand_thermal_kw": 5020,
        "shared_capacity_thermal_kw": 4800,
        "thermal_margin_kw": -220
      },
      {
        "start": "2026-10-26T13:00:00+00:00",
        "end": "2026-10-26T14:00:00+00:00",
        "heat_demand_thermal_kw": 4700,
        "shared_capacity_thermal_kw": 5100,
        "thermal_margin_kw": 400
      },
      {
        "start": "2026-10-26T14:00:00+00:00",
        "end": "2026-10-26T15:00:00+00:00",
        "heat_demand_thermal_kw": 4150,
        "shared_capacity_thermal_kw": 6100,
        "thermal_margin_kw": 1950
      }
    ],
    "thermal_assumptions": [
      "All IT electricity becomes heat inside the stated boundary; 70% of IT heat enters the liquid branch.",
      "Cooling and other electrical heat are included once; capacities apply at the supplied interval conditions.",
      "Mixed air/liquid path, adequate flow/distribution and one shared final rejection stage; no transient or redundancy model."
    ]
  }
}